Circutor R13862 Computer SMART III 12 Power Factor Regulator 12-Step RS-485
Doprava zdarma
Získejte dopravu zdarma při objednávce nad 300 €!
Circutor Computer SMART III 12 (code R13862) is a three-phase power factor regulator that controls 12 capacitor bank steps via contactors. Designed for installations with demanding compensation requirements, it operates across a power supply range of 100 to 520 V AC, communicates over RS-485 using Modbus RTU, and uniquely accepts either one or three current transformers for precise reactive energy regulation alongside integral power analysis and residual leakage current monitoring.
Technical specifications:
- Model: Computer SMART III 12
- Circutor code: R13862
- EAN: 8433059175115
- Number of steps: 12
- Switching unit: Contactor
- Power supply: 100...520 V AC, 50...60 Hz
- Consumption: 13...20 VA
- Installation category: CAT III 300 V
- Voltage measurement range: 20...300 V Ph-N, 35...520 V Ph-Ph
- Nominal measurement voltage: 230 V Ph-N, 400 V Ph-Ph
- Minimum measurement voltage: 20 V Ph-N, 35 V Ph-Ph
- Input current: .../5 A or .../1 A secondary
- Phase current measuring range: 1...120% of In
- Minimum current measurement: 50 mA
- Leakage current measurement range: 0.01...1.5 A
- Serial communication: Modbus RTU, RS-485
- Digital relay outputs: 14 total (12 step outputs, 1 fan, 1 alarm relay)
- Maximum relay current: 1 A
- Maximum relay switching capacity: 2500 VA
- Relay electrical life: 30 x 10³ cycles
- Relay mechanical life: 5 x 10⁶ cycles
- Digital transistor outputs: 2 x NPN, 50 mA, 24 V DC
- Digital inputs: 2, optoisolated, potential-free contact
- Active power measurement accuracy: 0.5% ± 1 digit
- Reactive energy accuracy: Class 1
- Active energy accuracy: 0.5% ± 2 digits
- Phase current accuracy: 0.5% ± 1 digit
- Display: Custom COG LCD with capacitive 5-key keyboard and 4 LEDs
- Size: 144 × 144 × 71 mm, panel mount
- Enclosure: Plastic V0 self-extinguishing
- Protection class: IP 51 front panel, IP 31 unmounted
- Working temperature: -10...+55 °C
- Storage temperature: -20...+70 °C
- Relative humidity: 5...95% non-condensing
- Maximum altitude: 2000 m
- Weight: 0.6 kg
- Standards: IEC 61010, IEC 61000-6-2, IEC 61000-6-4, IEC 61557-12
Features and benefits:
- Accepts one or three current transformers, enabling the regulator to mirror the utility meter's measurement method and deliver accurate compensation in unbalanced three-phase installations.
- Functions as an integral power analyzer, measuring active and reactive power and energy without requiring a separate instrument.
- Residual leakage current monitoring via compatible WG series current transformers provides early detection of insulation degradation as part of preventive maintenance.
- Programmable alarms combined with capacitor status testing allow continuous supervision of the compensation unit, helping to identify faults before they result in reactive energy penalties.
- Supports up to four target cos phi values across different time periods, making it adaptable to sites with variable consumption patterns or multi-tariff contracts.
Applications:
- Reactive power compensation in industrial and commercial capacitor banks requiring 12-step contactor switching control.
- Installations with significant load imbalances where a single current transformer cannot provide sufficiently accurate measurement across all three phases.
- Sites requiring combined power factor correction and power analysis within a single panel-mounted device.
- Medium voltage compensation units, where the wide 100 to 520 V AC supply range accommodates diverse transformer secondary voltages.