Schneider CAD32BL Control Relay,TeSys Deca, 3NO+2NC 24VDC
Doprava zdarma
Získejte dopravu zdarma při objednávce nad 300 €!
The Schneider Electric CAD32BL is a TeSys D auxiliary contactor with a 3 NO + 2 NC contact arrangement, designed for control circuit applications. Operating on a 24 V DC low-consumption coil, it is rated for voltages up to 690 V AC and offers a permissible thermal current of 10 A at 60 °C.
Technical specifications:
- Commercial reference: CAD32BL
- Manufacturer: Schneider Electric
- EAN:
- Series / range: TeSys D / TeSys Deca - TeSys CAD
- Product type: Auxiliary contactor (control relay)
- Contact arrangement: 3 NO + 2 NC
- Rated voltage: up to 690 V AC, 25...400 Hz
- Control circuit type: DC low consumption
- Control circuit voltage: 24 V DC
- Rated insulation voltage: 690 V (IEC 60947-5-1), 600 V (UL/CSA)
- Rated impulse withstand voltage: 6 kV (IEC 60947)
- Permissible thermal current: 10 A at 60 °C
- Rated making capacity: 140 A AC / 250 A DC (IEC 60947-5-1)
- Short-time withstand current: 100 A - 1 s / 120 A - 500 ms / 140 A - 100 ms
- Associated fuse: 10 A gG (IEC 60947-5-1)
- Mechanical endurance: 30 million operating cycles
- Maximum operating rate: 180 cycles/min
- Operating temperature: -40...60 °C (up to 70 °C with derating)
- Storage temperature: -60...80 °C
- Operating altitude: 0...3000 m
- IP protection: IP2x (VDE 0106)
- Dimensions (WxHxD): 45 x 77 x 93 mm
- Weight: 0.58 kg
- Mounting: DIN rail or panel
- Connection: Screw terminal blocks, 1...4 mm² flexible/solid conductors
- Tightening torque: 1.2 N.m
- Standards: EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, JIS C8201-5-1
- Certifications: CE, UKCA, UL, CSA, CB, CCC, EAC
- Warranty: 18 months
Features and benefits:
- Low-consumption 24 V DC coil with pick-up power of 2.4 W and holding power of 2.4 W at 20 °C
- Wide operating temperature range from -40 °C to 70 °C suits demanding industrial environments
- Fast switching times: 65...88 ms make (NO) and 14...25 ms break (NO) for responsive control circuit operation
- Non-overlap time of 1.5 ms between NC and NO contacts prevents simultaneous contact closure
- Minimum switching voltage of 17 V and minimum switching current of 5 mA enable reliable low-energy signal switching
- Insulation resistance greater than 10 MOhm ensures high dielectric integrity
Applications:
- Control circuit interlocking and signal multiplication in industrial automation panels
- Auxiliary switching in motor starter assemblies alongside TeSys D main contactors
- PLC output interface relays in machine control cabinets
- Status signalling and indication circuits in switchgear and distribution boards
Compliant with EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. Part of the Schneider Electric TeSys D range.