Přeskočit na obsah
Nemůžete najít, co hledáte? Kontaktujte nás!
Nemůžete najít, co hledáte? Kontaktujte nás!

Circutor M10521 EC72 FA ../5A Ammeter

podle CIRCUTOR

Doprava zdarma

Získejte dopravu zdarma při objednávce nad 300 €!

Původní cena €77,63 - Původní cena €77,63
Původní cena
€77,63
€77,63 - €77,63
Momentální cena €77,63

The Circutor EC72 FA ../5A (code M10521) is a moving iron AC ammeter with a built-in phase switch for panel installation. Designed to work with current transformers having a 5 A secondary output, it displays current on a 90° scale to class 1.5 accuracy in a compact 72 x 72 mm panel-mount format.

Technical specifications:

  • Model: EC72 FA ../5A
  • Circutor code: M10521
  • EAN: 8433059004484
  • Product type: AC ammeter with phase switch, moving iron
  • Measurement input: .../5 A (5 A CT secondary)
  • Scale: 90°, P2
  • Accuracy class: 1.5 %FE
  • Panel cutout size: 72 x 72 mm, depth 49.2 mm
  • Weight: 0.141 kg
  • Front protection: IP 52
  • Terminal protection: IP 00
  • Operating temperature: +10 to +30 °C
  • Storage temperature: -25 to +40 °C
  • True RMS measurement range: 100 mA to 100 A
  • Circuit consumption: 0.3 to 1.5 VA
  • Frequency range: 20 to 100 Hz
  • Continuous overload capacity: 1.2 In
  • Short-term overload: 5 In for 30 s / 10 In for 5 s / 40 In for 1 s
  • Insulation voltage: 2 kV at 50 Hz (less than 1 min)
  • Certifications: CE
  • Standards: BS 89, UNE-EN 60051, IEC 144, DIN 43780, IEC 51, UNE 21318
  • Auxiliary power supply: not required

Features and benefits:

  • Operates without an auxiliary power supply, drawing all necessary operating power from the measurement circuit and reducing panel wiring complexity.
  • Scales are interchangeable with the EC48, EC72, EC96, EM 45, EC 72 FA, and EC 96 FA instrument series, minimising spare-parts inventory across a panel installation.
  • Short-term overload tolerance up to 40 In for 1 second protects the instrument during fault current events without requiring replacement.
  • IP 52 front protection shields the dial from dust ingress and water splash, maintaining readability in switchboard environments.
  • A frequency range of 20 to 100 Hz allows use beyond the standard 50 Hz grid, accommodating varied AC system frequencies.

Applications:

  • Monitoring individual phase currents on low-voltage switchboards and distribution panels via 5 A CT secondaries.
  • Motor control centres and industrial control cabinets requiring clear visual current indication with phase selection capability.
  • Building electrical distribution boards specifying a 72 x 72 mm DIN panel-mount instrument format.
  • AC installations where a self-powered panel ammeter is needed without additional auxiliary supply wiring.

Also known as: Circutor EC72 FA ../5A, EC72 FA M10521, Circutor M10521, moving iron panel ammeter, phase switch ammeter 5A.