Schneider A9R61440 Residual current circuit breaker (RCCB), Acti9 iID, 4P, 40A,
Doprava zdarma
Získejte dopravu zdarma při objednávce nad 300 €!
The Schneider Electric A9R61440 is a 4-pole Residual Current Circuit Breaker (RCCB) from the Acti 9 iID series, rated at 40A with a 30mA residual current sensitivity. Designed for AC networks, it provides selective (SI type) earth fault protection with immediate tripping response for reliable downstream circuit safety.
Technical specifications:
- Commercial reference: A9R61440
- Manufacturer: Schneider Electric
- EAN:
- Series / range: Acti 9 iID
- Product type: Residual Current Circuit Breaker (RCCB)
- Number of poles: 4P
- Neutral position: Left
- Rated current [In]: 40 A
- Network type: AC
- Residual current sensitivity: 30 mA
- Tripping delay: Instantaneous
- Residual current class: Type A-SI
- Rated voltage [Ue]: 380...415 V AC 50/60 Hz
- Network frequency: 50/60 Hz
- Rated making/breaking capacity: Idm 1500 A / Im 1500 A
- Rated conditional short-circuit current: 10 kA
- Rated insulation voltage [Ui]: 500 V AC 50/60 Hz
- Rated impulse withstand voltage [Uimp]: 6 kV
- Impulse current: 3000 A
- Mounting: DIN rail, clip-on system
- DIN rail rows: 9 mm, 8 modules wide
- Dimensions (HxWxD): 91 x 72 x 73.5 mm
- Weight: 0.37 kg
- IP rating: IP20 (IEC 60529), IP40 in modular enclosure (IEC 60529)
- Operating temperature: -25...60 °C
- Storage temperature: -40...85 °C
- Connection: Single terminal block, top or bottom, 1...35 mm² rigid / 1...25 mm² flexible
- Tightening torque: 3.5 N.m
- Mechanical endurance: 20,000 cycles
- Electrical endurance: 15,000 cycles (AC-1)
- Standards: EN/IEC 61008-1, EN/IEC 61008-2-1
- Certifications: CCC
Features and benefits:
- Type A-SI residual current class provides selectivity, preventing unwanted upstream tripping in tiered protection schemes
- Instantaneous tripping at 30 mA ensures fast earth fault disconnection to protect against electric shock
- Independent tripping technology operates without reliance on the mains voltage supply
- Clip-on DIN rail mounting enables quick, tool-free installation in modular enclosures
- Contact position indicator provides clear visual confirmation of open or closed state
- EMC-rated to withstand 8/20 µs impulse current of 3000 A per EN/IEC 61008-1
Applications:
- Final distribution boards in residential and commercial buildings requiring 4-pole earth fault protection
- Three-phase + neutral circuits where selective RCD coordination with upstream devices is required
- Industrial control panels and distribution switchboards operating on 380...415 V AC networks
- Installations requiring protection against both sinusoidal and pulsating DC residual currents (Type A)
Compliant with EN/IEC 61008-1 and EN/IEC 61008-2-1. Part of the Schneider Electric Acti 9 range.
Also known as: Schneider A9R61440, Schneider Electric A9R61440, Acti9 iID 4P 40A 30mA RCCB, Schneider 4-pole residual current device.
Když je vyprodáno, můžete si stále předobjednat žádostí o cenovou nabídku níže.
Důležité
Zobrazené obrázky slouží pouze pro ilustraci a nemusí přesně odpovídat produktu.