Telemecanique XCKP2511P16 Limit Switch End Plunger Nitrile Boot 1NC+1NO M16

Free Shipping

Get free shipping on orders exceeding €300!

Original price €21,44 - Original price €21,44
Original price
€21,44
€21,44 - €21,44
Current price €21,44

The Telemecanique XCKP2511P16 is an XC Standard XCKP limit switch with a metal end plunger with nitrile boot. It has 1 NC + 1 NO contacts (slow-break, break before make) and 1 entry tapped for M16 x 1.5 cable gland. The NC contact has positive opening operation. Degree of protection: IP66 conforming to IEC 60529.

Technical specifications:

  • Commercial reference: XCKP2511P16
  • Manufacturer: Telemecanique Sensors
  • EAN: 3389110204223
  • Range: Telemecanique Limit switches XC Standard
  • Series: Standard format
  • Product type: Limit switch
  • Device short name: XCKP
  • Sensor design: Compact
  • Body type: Fixed
  • Head type: Plunger head
  • Body material: Plastic
  • Head material: Zamak
  • Movement of operating head: Linear
  • Type of operator: Spring return roller plunger metal with nitrile boot
  • Type of approach: Vertical approach, 1 direction
  • Number of poles: 2
  • Contacts type and composition: 1 NC + 1 NO
  • Contact operation: Slow-break, break before make
  • Switch actuation: On end
  • Terminal marking: (13-14)NO; (21-22)NC
  • Electrical connection: Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
  • Cable entry: 1 entry tapped for M16 x 1.5 cable gland, cable outer diameter: 4...8 mm
  • Positive opening: With
  • Positive opening minimum force: 45 N
  • Minimum force for tripping: 15 N
  • Maximum actuation speed: 0.5 m/s
  • Repeat accuracy: 0.1 mm on the tripping points with 1 million operating cycles
  • Contact rating: A300, AC-15 (Ue = 240 V), Ie = 3 A, Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A; Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1 appendix A
  • Rated insulation voltage [Ui]: 300 V conforming to UL 508; 500 V (pollution degree 3) conforming to IEC 60947-1; 300 V conforming to CSA C22.2 No 14
  • Rated impulse withstand voltage [Uimp]: 6 KV conforming to IEC 60664; 6 kV conforming to IEC 60947-1
  • Short-circuit protection: 10 A cartridge fuse, type gG
  • Mechanical durability: 15000000 cycles
  • Width: 31 mm
  • Height: 65 mm
  • Depth: 30 mm
  • IP degree of protection: IP66 conforming to IEC 60529; IP67 conforming to IEC 60529
  • IK degree of protection: IK04 conforming to EN 50102
  • Operating temperature: -25...70 °C
  • Storage temperature: -40...70 °C
  • Certifications: CSA, CCC, UL
  • Standards: CSA C22.2 No 14, EN 60204-1, IEC 60204-1, IEC 60947-5-1, EN 60947-5-1, UL 508