Schneider A9F84204 Acti9 iC60H MCB 2P C 4A 10kA
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric A9F84204 is a 2-pole miniature circuit breaker (MCB) from the Acti9 iC60H range, rated 4 A with a C tripping curve. It provides thermal-magnetic overload and short-circuit protection with a breaking capacity of 10,000 A at 400 V AC to EN/IEC 60898-1 and is suitable for isolation.
Technical specifications:
- Reference: A9F84204
- Range: Acti 9
- Model: iC60H
- Type: Miniature circuit breaker (MCB)
- Poles: 2P, 2 protected poles
- Rated current (In): 4 A
- Tripping curve: C
- Network type: AC and DC
- Trip unit technology: thermal-magnetic
- Magnetic tripping limit: 8 x In +/-20 %
- Breaking capacity (Icn): 10,000 A at 400 V AC 50/60 Hz to EN/IEC 60898-1
- Breaking capacity (Icu) to EN/IEC 60947-2: 70 kA at 12-133 V AC, 220-240 V AC and 380-415 V AC, 50 kA at 440 V AC, 15 kA at up to 125 V DC
- Service breaking capacity (Ics): 100 % of Icu to EN/IEC 60947-2, 7500 A (75 %) at 400 V AC to EN/IEC 60898-1
- Limitation class: 3
- Utilisation category: Category A
- Suitable for isolation: yes
- Rated insulation voltage (Ui): 500 V AC
- Rated impulse withstand voltage (Uimp): 6 kV
- Contact position indicator: yes
- Local signalling: trip indicator
- Mounting: DIN rail, fixed
- Comb busbar: top or bottom
- Width in 9 mm modules: 4
- Connection: 1 to 25 mm² rigid, 1 to 16 mm² flexible, strip length 14 mm, tightening torque 2 N.m
- Mechanical durability: 20,000 cycles
- Electrical durability: 10,000 cycles
- Degree of protection: IP20
- Pollution degree: 3
- Overvoltage category: IV
- Operating temperature: -35 to 70 °C
- Storage temperature: -40 to 85 °C
- Dimensions (H x W x D): 85 x 36 x 78.5 mm
- Colour: white
- Standards: EN/IEC 60898-1, EN/IEC 60947-2
- EAN: 3606480082528
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.