LVR05X00A69T Anti Harmonic PowerLogic PFC detuned reactor, 100kvar 210Hz (4.2) 5.7% 50Hz 690V
The VarPlus detuned reactor are designed to protect the capacitor by preventing the amplification of the harmonics present in the system. Capacitors and Reactors are configured in Series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This reactor is rated for 100 kVar output power with 4.2/210 Hz tuning order at 690V AC at 50 Hz. Relative impedance, 5.7 %. This component meet the standards IEC 60068. This component require a forced convection, a fan need to be added. The case dimensions are 350mm in height, 350mm in width and 220mm in depth. For a product weight of 42 kg.
Business customers from EU, please contact us or log in to benefit from tax exemptions.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.