Schneider LRD01 TeSys Deca Thermal Overload Relay 0.1-0.16A
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric LRD01 is a TeSys LRD differential thermal overload relay designed for motor protection, with a current setting range of 0.1 to 0.16 A and tripping class 10A per IEC 60947-4-1. It mounts directly below compatible TeSys D contactors and operates on both AC and DC networks across the full frequency range of 0 to 400 Hz.
Technical specifications:
- Commercial reference: LRD01
- Manufacturer: Schneider Electric
- EAN:
- Series / range: TeSys LRD / TeSys Deca
- Product type: Differential thermal overload relay
- Relay function: Motor protection
- Thermal overload setting: 0.1...0.16 A
- Tripping class: Class 10A per IEC 60947-4-1
- Tripping threshold: 1.14 +/- 0.06 Ir per IEC 60947-4-1
- Network type: AC / DC
- Network frequency: 0...400 Hz
- Rated voltage [ue]: 690 V AC for power circuit per IEC 60947-4-1
- Rated insulation voltage [ui]: 690 V per IEC 60947-4-1; 600 V per UL / CSA
- Rated impulse withstand voltage [uimp]: 6 kV
- Auxiliary contact: 1 NO + 1 NC
- Thermal current [ith]: 5 A for signal circuit
- Associated fuse: 4 A gG / 4 A BS for signal circuit
- Control: Red button (stop), Blue button (reset)
- Connection type: Screw terminal blocks - power circuit 1 cable 1...6 mm² single-core; control circuit 2 cables 1...2.5 mm²
- Tightening torque: 1.7 N.m (power and control circuits)
- Compatible contactors: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38
- Mounting: Below contactor, plate or DIN rail (with accessories)
- Dimensions (W x H x D): 45 x 66 x 70 mm
- Weight: 0.124 kg
- IP protection: IP20 per IEC 60529
- Operating temperature: -20...60°C per IEC 60947-4-1
- Storage temperature: -60...70°C
- Dielectric strength: 1.89 kV at 50 Hz per IEC 60947-1
- Flame resistance: V1 per UL 94
- Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA
Features and benefits:
- Phase loss sensitivity: triggers at 130% of Ir with two phases active and the third at zero
- Temperature compensation across -20...60°C ensures consistent tripping characteristics
- Direct mounting below TeSys D contactors reduces panel space and wiring
- Vibration resistance to 6 Gn and shock resistance to 15 Gn for 11 ms suits demanding industrial environments
- Wide certification portfolio including ATEX INERIS and marine classifications (DNV-GL, RINA, LROS)
Applications:
- Protection of small fractional-horsepower motors in conveyor and automation systems
- Motor starter assemblies paired with TeSys D LC1D contactors in control panels
- HVAC and pump motor circuits requiring reliable thermal overload protection
- Marine and hazardous-area installations requiring ATEX or marine-certified components
Compliant with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and EN 50495. Part of the Schneider Electric TeSys Deca range.