Schneider A9F74313 Acti9 iC60N MCB 3P 13 A C Curve 10kA
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric A9F74313 is a 3-pole miniature circuit breaker (MCB) from the Acti 9 iC60N series, rated at 13 A with a C tripping curve. It provides thermomagnetic overload and short-circuit protection for AC and DC distribution networks, with a breaking capacity of 10 kA at 380-415 V AC per IEC 60947-2.
Technical specifications:
- Commercial reference: A9F74313
- Manufacturer: Schneider Electric
- EAN:
- Series / range: Acti 9 iC60N
- Number of poles: 3P, 3 protected poles
- Rated current [In]: 13 A
- Tripping curve: C
- Network type: AC and DC
- Protection technology: Thermomagnetic
- Breaking capacity: 6000 A Icn at 400 V AC per EN/IEC 60898-1; 10 kA Icu at 380-415 V AC per EN/IEC 60947-2; 20 kA Icu at 220-240 V AC per EN/IEC 60947-2
- Rated insulation voltage [Ui]: 500 V AC 50/60 Hz
- Rated impulse withstand voltage [Uimp]: 6 kV
- Limitation class: 3 per EN/IEC 60898-1
- Usage category: Category A per EN/IEC 60947-2
- IP protection rating: IP20 per IEC/EN 60529
- Pollution degree: 3
- Overvoltage category: IV
- Operating temperature: -35 to 70°C
- Storage temperature: -40 to 85°C
- Mounting: DIN rail, fixed
- Dimensions (WxHxD): 54 x 85 x 78.5 mm
- Weight: 0.375 kg
- Connection: 1-25 mm² rigid / 1-16 mm² flexible; strip length 14 mm; tightening torque 2 N.m
- Mechanical durability: 20,000 cycles; electrical durability: 10,000 cycles
Features and benefits:
- C curve thermomagnetic protection with overcurrent trip threshold at 8 x In (+/- 20%)
- Suitable for use as an isolator per EN/IEC 60898-1 and EN/IEC 60947-2
- Compatible with comb busbar distribution blocks on upper or lower connection
- Built-in trip indicator and contact position indicator for fast fault identification
- Wide operating temperature range of -35 to 70°C suits demanding installation environments
- Tropicalization class 2 per IEC 60068-1, rated for 95% relative humidity at 55°C
Applications:
- Final distribution boards in commercial and industrial buildings
- Outgoing circuit protection in main and sub-distribution panels
- Motor and equipment circuit protection in automation and control panel assemblies
- AC and DC distribution systems requiring compact DIN rail-mounted overcurrent protection
Compliant with IEC 60947-2, EN 60947-2, IEC 60898-1, and EN 60898-1. Part of the Schneider Electric Acti 9 range.
Also known as: Schneider A9F74313, Schneider Electric A9F74313, Acti9 iC60N 3-pole MCB 13A C curve.