Circutor M78038 TP10 Split Core Current Transformer 1500/5A, 80x120mm
Free Shipping
Get free shipping on orders exceeding €300!
The Circutor TP10 1500/5 (code M78038) is a split core measurement current transformer with a 1500/5 A transformation ratio and an 80 × 120 mm flat strip aperture. Designed for single-phase current measurement on both cables and busbars, it can be fitted around live conductors without disconnecting the supply, making retrofit installation straightforward.
Technical specifications:
- Model: TP10 1500/5
- Circutor code: M78038
- EAN: 8433059401658
- Transformer type: Split core
- System: Single-phase
- Measurement range: 1500/5 A
- Flat strip aperture: 80 × 120 mm
- Inner diameter: 80 mm
- Class 0.5 power: 8 VA
- Class 1 power: 17 VA
- Class 3 power: 30 VA
- Safety factor (SF): 10
- Insulation voltage between terminals S1-S2: 3 kV
- Operating voltage: 0.72 kV~ max.
- Nominal frequency: 50/60 Hz
- Thermal short-circuit current (Ith): 60 In
- Dynamic current (Idyn): 2.5 Ith
- Housing dimensions: 158 × 51 × 193.8 mm
- Enclosure material: V0 self-extinguishing plastic
- Protection class: IP 20
- Thermal class: Class B (+130 °C)
- Working temperature: -5 to +40 °C
- Storage temperature: -40 to +85 °C
- Relative humidity: 15 to 85% (non-condensing)
- Weight: 0.55 kg
- Mounting: Wall or DIN rail (accessory required)
- Maximum installation altitude: 1000 m
- Standards: UNE-EN 61869-1, UNE-EN 61869-2, UL 94
Features and benefits:
- Split core construction allows installation around energised conductors without shutting down the circuit, eliminating costly outages during metering upgrades.
- Accepts flat busbars up to 80 × 120 mm, covering a wide range of high-current switchboard configurations.
- Integrated safety lock on the TP-10 model prevents the core from opening unintentionally once closed around the conductor.
- Sealable secondary terminals and cable fastening accessories are included as standard, supporting tamper-evident revenue metering setups.
- V0 self-extinguishing plastic housing meets fire-resistance requirements for installation inside electrical enclosures.
Applications:
- Retrofit energy metering and submetering in industrial or commercial facilities where interrupting the power supply is not an option.
- Current input for protection relays and measuring instruments in LV switchboards carrying large busbar sections up to 80 × 120 mm.
- Revenue-grade billing metering at Class 0.5 accuracy for energy management systems requiring traceable measurement.
- Monitoring of high-current feeders up to 1500 A in manufacturing plants, data centres, or utility distribution panels.
Also known as: Circutor TP10 1500/5, TP10 1500/5 M78038, split core current transformer 1500A, Circutor M78038, split core CT 80x120mm.