Schneider LRD22 TeSys Deca Thermal Overload Relay 16-24A
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric LRD22 is a thermal overload relay from the TeSys Deca range, designed for motor protection in AC and DC circuits. With an adjustable setting of 16 to 24 A and Class 10A tripping per IEC 60947-4-1, it protects motors against overload and phase loss. Compatible with LC1D25, LC1D32, and LC1D38 contactors, it mounts directly below the contactor for compact starter assemblies.
Technical specifications:
- Commercial reference: LRD22
- Manufacturer: Schneider Electric
- EAN:
- Series / range: TeSys Deca (TeSys LRD)
- Thermal overload setting: 16...24 A
- Tripping class: Class 10A per IEC 60947-4-1
- Network type: AC / DC, 0...400 Hz
- Rated insulation voltage [Ui]: 690 V (IEC 60947-4-1), 600 V (UL / CSA)
- Rated operational voltage [Ue]: 690 V AC per IEC 60947-4-1
- Phase loss sensitivity: 130% of Ir in two phases, last phase at 0
- Auxiliary contact: 1 NO + 1 NC
- Mounting: below contactor; DIN rail or panel plate with accessories
- Dimensions (W x H x D): 45 x 66 x 70 mm
- Weight: 0.124 kg
- IP rating: IP20 per IEC 60529
- Operating temperature: -20...60 °C per IEC 60947-4-1
- Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, ATEX INERIS, UKCA, LROS
Features and benefits:
- Phase loss detection trips at 130% of Ir in two phases, preventing motor burnout from single-phasing
- Mounts directly below LC1D25 / LC1D32 / LC1D38 contactors for compact, wiring-free starter assembly
- 1 NO + 1 NC auxiliary contact enables fault signalling and remote trip indication
- Temperature compensation across -20...60 °C maintains consistent tripping accuracy in varying ambient conditions
- Frequency range of 0...400 Hz supports both standard supplies and variable-frequency drive outputs
Applications:
- Motor starters in industrial automation and control panels
- Protection of pumps, fans, compressors, and conveyor drive motors
- Motor control centres using TeSys D contactor and overload relay assemblies
- Marine and hazardous area installations requiring DNV-GL, BV, or ATEX INERIS certification
Compliant with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN 50495. Part of the Schneider Electric TeSys Deca range.
Also known as: Schneider LRD22, Schneider Electric LRD22, TeSys thermal overload relay 16-24A.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.