Schneider A9F84102 Miniature Circuit Breaker (MCB), Acti9 iC60H 1P C2A 10kA
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric A9F84102 is a 1-pole miniature circuit breaker (MCB) from the Acti 9 iC60H range, rated at 2 A with a C tripping curve and a breaking capacity of 10 kA at 230 V AC. Designed for both AC and DC network types, it provides thermomagnetic protection suitable for electrical distribution applications.
Technical specifications:
- Commercial reference: A9F84102
- Manufacturer: Schneider Electric
- EAN:
- Series / range: Acti 9 iC60
- Product type: Miniature circuit breaker (MCB)
- Short device name: iC60H
- Number of poles: 1P
- Number of protected poles: 1
- Rated current (In): 2 A
- Tripping curve: C
- Network type: AC / DC
- Protection unit technology: Thermomagnetic
- Breaking capacity (Icn): 10 kA at 230 V AC 50/60 Hz per EN/IEC 60898-1
- Breaking capacity (Icu): 15 kA at 72 V DC per EN/IEC 60947-2
- Breaking capacity (Icu): 20 kA at 12-60 V DC per EN/IEC 60947-2
- Breaking capacity (Icu): 70 kA at 220-240 V AC 50/60 Hz per EN/IEC 60947-2
- Service breaking capacity (Ics): 70 kA at 220-240 V AC 50/60 Hz per EN/IEC 60947-2
- Limitation class: 3 per EN/IEC 60898-1
- Rated insulation voltage (Ui): 500 V AC 50/60 Hz per EN/IEC 60947-2
- Rated impulse withstand voltage (Uimp): 6 kV per EN/IEC 60947-2
- Overcurrent protection limit: 8 x In +/- 20%
- Width: 18 mm
- Height: 85 mm
- Depth: 78.5 mm
- Weight: 0.215 kg
- IP rating: IP20 per IEC/EN 60529
- Operating temperature: -35 to 70 °C
- Storage temperature: -40 to 85 °C
- Relative humidity: 95% at 55 °C
- Mounting: DIN rail
- Connection: Single terminal block (top or bottom), 1-25 mm² rigid / 1-16 mm² flexible
- Strip length: 14 mm
- Tightening torque: 2 N.m
- Mechanical durability: 20,000 cycles
- Electrical durability: 10,000 cycles
- Overvoltage category: IV
- Standards: EN/IEC 60947-2, EN/IEC 60898-1
- Warranty: 18 months
Features and benefits:
- Suitable for isolation per EN/IEC 60898-1 and EN/IEC 60947-2, enabling safe maintenance procedures
- Compatible with comb busbar distribution blocks from both top and bottom connections
- Contact position indicator and trip indicator for quick local status monitoring
- Limitation class 3 for high energy limiting performance, reducing let-through energy during faults
- Wide operating temperature range (-35 to 70 °C) for reliable performance in demanding environments
- Use category A per EN/IEC 60947-2, suitable for applications without intentional short-circuit current limiting
Applications:
- Final distribution boards in residential and commercial electrical installations
- Protection of low-current circuits and sensitive loads in electrical panels
- DC distribution systems requiring circuit protection at 12-72 V DC
- Industrial control panels requiring thermomagnetic overcurrent protection
- Switchboards where DIN rail mounting and compact 18 mm width are required
Compliant with EN/IEC 60947-2 and EN/IEC 60898-1. Part of the Schneider Electric Acti 9 iC60 range.
Also known as: Schneider A9F84102, Schneider Electric A9F84102, Acti9 iC60H 1P C2A MCB, Schneider 2A C-curve miniature circuit breaker.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.