Skip to content
Can't find what you're looking for? Reach out to us!
Can't find what you're looking for? Reach out to us!

Schneider C103TM050 ComPacT NSX100 Trip Unit 3P 50 A TMD

Free Shipping

Get free shipping on orders exceeding €300!

Original price $44.54 - Original price $44.54
Original price
$44.54
$44.54 - $44.54
Current price $44.54

The Schneider Electric C103TM050 is a TMD trip unit designed for use with ComPacT NSX100/160 circuit breakers. This 3-pole thermomagnetic protection unit provides both overload (thermal) and short-circuit (instantaneous) protection, rated at 50 A at 40°C for power distribution applications.

Technical specifications:

  • Commercial reference: C103TM050
  • Manufacturer: Schneider Electric
  • EAN:
  • Series / range: ComPacT NSX100/160 (new generation)
  • Trip unit name: TM-D
  • Trip unit technology: Thermomagnetic
  • Number of poles: 3P
  • Protected poles: 3d
  • Trip unit rating: 50 A at 40°C
  • Rated voltage [Ue]: 690 V AC 50/60 Hz / 750 V DC
  • Network type: AC / DC
  • Network frequency: 50/60 Hz
  • Mounting mode: Fixed
  • Protection function: L (overload) + I (short-circuit)
  • Long-time pick-up [Ir]: Adjustable, 0.7 to 1 x In
  • Long-time delay [tr]: Fixed, 120 to 400 seconds at 1.5 x In; 15 seconds at 6 x Ir
  • Instantaneous pick-up [Ii]: Fixed, 500 A
  • Differential protection: None
  • Standard: EN/IEC 60947-2
  • Electric shock protection class: Class II
  • Pollution degree: 3 per IEC 60947-1
  • IP protection rating: IP40 per IEC 60529
  • Operating temperature: -25 to 70°C
  • Storage temperature: -50 to 85°C
  • Weight: 412 g

Features and benefits:

  • Thermomagnetic technology delivers reliable dual-function protection against both overload and short-circuit faults
  • Adjustable long-time pick-up (Ir) from 0.7 to 1 x In allows fine-tuning of thermal protection threshold
  • Compatible with both AC and DC networks up to 690 V AC and 750 V DC
  • IP40 enclosure and Class II electric shock protection rating suit demanding industrial environments
  • Wide operating temperature range (-25 to 70°C) ensures reliable performance across varied installation conditions

Applications:

  • Power distribution panels requiring coordinated overload and short-circuit protection
  • Industrial installations using ComPacT NSX100 or NSX160 circuit breakers in fixed mounting configurations
  • AC and DC distribution systems in manufacturing, infrastructure, or commercial facilities
  • Retrofit or replacement trip unit for existing ComPacT NSX100/160 frames

Compliant with EN/IEC 60947-2. Part of the Schneider Electric ComPacT NSX new generation range.

Also known as: Schneider C103TM050, Schneider Electric C103TM050, NSX100 TMD trip unit, ComPacT NSX thermomagnetic protection unit.

When sold out, you can still preorder by requesting a quote below.

Click here to request a quote

Important

The images shown are for illustration purposes only and may not be an exact
representation of the product.