Schneider A9F74313 Acti9 iC60N MCB 3P 13 A C Curve 10kA

Free Shipping

Get free shipping on orders exceeding €300!

Original price $11.99 - Original price $11.99
Original price
$11.99
$11.99 - $11.99
Current price $11.99

The Schneider Electric A9F74313 is a 3-pole miniature circuit breaker (MCB) from the Acti 9 iC60N series, rated at 13 A with a C tripping curve. It provides thermomagnetic overload and short-circuit protection for AC and DC distribution networks, with a breaking capacity of 10 kA at 380-415 V AC per IEC 60947-2.

Technical specifications:

  • Commercial reference: A9F74313
  • Manufacturer: Schneider Electric
  • EAN:
  • Series / range: Acti 9 iC60N
  • Number of poles: 3P, 3 protected poles
  • Rated current [In]: 13 A
  • Tripping curve: C
  • Network type: AC and DC
  • Protection technology: Thermomagnetic
  • Breaking capacity: 6000 A Icn at 400 V AC per EN/IEC 60898-1; 10 kA Icu at 380-415 V AC per EN/IEC 60947-2; 20 kA Icu at 220-240 V AC per EN/IEC 60947-2
  • Rated insulation voltage [Ui]: 500 V AC 50/60 Hz
  • Rated impulse withstand voltage [Uimp]: 6 kV
  • Limitation class: 3 per EN/IEC 60898-1
  • Usage category: Category A per EN/IEC 60947-2
  • IP protection rating: IP20 per IEC/EN 60529
  • Pollution degree: 3
  • Overvoltage category: IV
  • Operating temperature: -35 to 70°C
  • Storage temperature: -40 to 85°C
  • Mounting: DIN rail, fixed
  • Dimensions (WxHxD): 54 x 85 x 78.5 mm
  • Weight: 0.375 kg
  • Connection: 1-25 mm² rigid / 1-16 mm² flexible; strip length 14 mm; tightening torque 2 N.m
  • Mechanical durability: 20,000 cycles; electrical durability: 10,000 cycles

Features and benefits:

  • C curve thermomagnetic protection with overcurrent trip threshold at 8 x In (+/- 20%)
  • Suitable for use as an isolator per EN/IEC 60898-1 and EN/IEC 60947-2
  • Compatible with comb busbar distribution blocks on upper or lower connection
  • Built-in trip indicator and contact position indicator for fast fault identification
  • Wide operating temperature range of -35 to 70°C suits demanding installation environments
  • Tropicalization class 2 per IEC 60068-1, rated for 95% relative humidity at 55°C

Applications:

  • Final distribution boards in commercial and industrial buildings
  • Outgoing circuit protection in main and sub-distribution panels
  • Motor and equipment circuit protection in automation and control panel assemblies
  • AC and DC distribution systems requiring compact DIN rail-mounted overcurrent protection

Compliant with IEC 60947-2, EN 60947-2, IEC 60898-1, and EN 60898-1. Part of the Schneider Electric Acti 9 range.

Also known as: Schneider A9F74313, Schneider Electric A9F74313, Acti9 iC60N 3-pole MCB 13A C curve.