Schneider LRD07 Electric LRD07 TeSys Deca Thermal Overload Relay 1.6-2.5 A

Free Shipping

Get free shipping on orders exceeding €300!

Original price $35.86 - Original price $35.86
Original price
$35.86
$35.86 - $35.86
Current price $35.86

The Schneider Electric LRD07 is a TeSys LRD differential thermal overload relay for motor protection, with a current adjustment range of 1.6 to 2.5 A and Class 10A tripping per IEC 60947-4-1. Rated for power circuits up to 690 V AC across 0 to 400 Hz, it mounts directly below compatible TeSys Deca contactors for a compact panel assembly.

Technical specifications:

  • Commercial reference: LRD07
  • Manufacturer: Schneider Electric
  • EAN:
  • Series / range: TeSys LRD / TeSys Deca
  • Product type: Differential thermal overload relay
  • Application: Motor protection
  • Current adjustment range: 1.6...2.5 A
  • Tripping class: Class 10A per IEC 60947-4-1
  • Rated voltage [Ue]: 690 V AC, 0...400 Hz per IEC 60947-4-1
  • Rated insulation voltage [Ui]: 690 V (IEC 60947-4-1); 600 V (UL / CSA)
  • Rated impulse withstand voltage [Uimp]: 6 kV
  • Network type: AC / DC
  • Tripping threshold: 1.14 +/- 0.06 Ir per IEC 60947-4-1
  • Phase loss tripping current: 130% of Ir in two phases, last phase at 0
  • Auxiliary contact: 1 NO + 1 NC
  • Permissible thermal current [Ith]: 5 A (control circuit)
  • Mounting: Below contactor; panel or DIN rail with accessory
  • Connection: Screw terminal blocks - power circuit 1.5...10 mm², control circuit 1...2.5 mm²
  • Tightening torque: 1.7 N.m (power and control circuits)
  • Dimensions (W x H x D): 45 x 66 x 70 mm
  • Weight: 0.124 kg
  • IP protection: IP20 per IEC 60529
  • Operating temperature: -20...60 °C per IEC 60947-4-1
  • Storage temperature: -60...70 °C
  • Compatible contactors: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38
  • Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA

Features and benefits:

  • Class 10A tripping characteristic provides reliable motor overload protection per IEC 60947-4-1
  • Phase loss sensitivity trips at 130% of Ir in two phases, protecting motors from single-phase operation
  • Temperature compensation across -20 to 60 °C maintains accurate tripping performance over a wide ambient range
  • Direct below-contactor mounting reduces panel space and simplifies wiring
  • Red stop button and blue reset button allow direct manual control and local reset

Applications:

  • Motor overload protection in industrial automation and machine control panels
  • Thermal protection for pump, fan, and compressor motor circuits
  • Marine and offshore control panels (certified by DNV-GL, BV, RINA, and LROS)
  • Hazardous area installations requiring ATEX-certified overload protection

Compliant with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and EN 50495. Part of the Schneider Electric TeSys Deca range.

Also known as: Schneider LRD07, Schneider Electric LRD07, TeSys thermal overload relay, motor protection relay 2.5A.