Schneider A9F74206 Acti9 iC60N MCB 2P 6 A C Curve 10kA
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric A9F74206 is a 2-pole, 6 A thermomagnetic miniature circuit breaker (MCB) from the Acti 9 iC60N range, designed for overcurrent protection in AC and DC electrical distribution networks. Its C tripping curve delivers a breaking capacity of 10 kA Icu at 380-415 V AC per IEC 60947-2 and 6,000 A Icn at 400 V AC per IEC 60898-1.
Technical specifications:
- Commercial reference: A9F74206
- Manufacturer: Schneider Electric
- EAN:
- Series / range: Acti 9 iC60
- Product type: Miniature circuit breaker (MCB)
- Short device name: iC60N
- Number of poles: 2P
- Number of protected poles: 2
- Rated current [In]: 6 A
- Tripping curve: C
- Network type: AC / DC
- Protection technology: Thermomagnetic
- Breaking capacity: 6,000 A Icn at 400 V AC (IEC/EN 60898-1); 10 kA Icu at 380-415 V AC; 20 kA Icu at 220-240 V AC (IEC/EN 60947-2)
- Overcurrent protection limit: 8 x In +/- 20%
- Limitation class: 3 (IEC/EN 60898-1)
- Rated insulation voltage [Ui]: 500 V AC
- Rated impulse withstand voltage [Uimp]: 6 kV
- Dimensions (WxHxD): 36 x 85 x 78.5 mm
- Weight: 0.25 kg
- Mounting: DIN rail, fixed
- Connection terminals: 1-25 mm² rigid / 1-16 mm² flexible; strip length 14 mm; tightening torque 2 N.m
- IP protection rating: IP20 (IEC/EN 60529)
- Operating temperature: -35 to 70°C
- Storage temperature: -40 to 85°C
- Mechanical durability: 20,000 cycles
- Electrical durability: 10,000 cycles
- Overvoltage category: IV
- Pollution degree: 3
Features and benefits:
- Suitable for use as an isolator per EN/IEC 60898-1 and EN/IEC 60947-2
- Trip indicator for local signaling of fault conditions
- Compatible with comb busbar distribution blocks on upper or lower terminals
- Limitation class 3 provides energy-limiting performance to reduce downstream damage
- Tropicalization class 2 and 95% relative humidity rating support use in demanding environments
Applications:
- Final distribution boards in residential and commercial buildings
- Industrial control panels and power distribution switchboards
- DIN rail-mounted circuit protection in automation enclosures
- AC and DC system overcurrent protection up to 415 V
Compliant with EN 60898-1, IEC 60898-1, EN 60947-2, and IEC 60947-2. Part of the Schneider Electric Acti 9 iC60 range.
Also known as: Schneider A9F74206, Schneider Electric A9F74206, iC60N 2P 6A C curve MCB, Acti9 miniature circuit breaker 6A.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.