Schneider LRD01 TeSys Deca Thermal Overload Relay 0.1-0.16A

Free Shipping

Get free shipping on orders exceeding €300!

Original price $34.09 - Original price $34.09
Original price
$34.09
$34.09 - $34.09
Current price $34.09

The Schneider Electric LRD01 is a TeSys LRD differential thermal overload relay designed for motor protection, with a current setting range of 0.1 to 0.16 A and tripping class 10A per IEC 60947-4-1. It mounts directly below compatible TeSys D contactors and operates on both AC and DC networks across the full frequency range of 0 to 400 Hz.

Technical specifications:

  • Commercial reference: LRD01
  • Manufacturer: Schneider Electric
  • EAN:
  • Series / range: TeSys LRD / TeSys Deca
  • Product type: Differential thermal overload relay
  • Relay function: Motor protection
  • Thermal overload setting: 0.1...0.16 A
  • Tripping class: Class 10A per IEC 60947-4-1
  • Tripping threshold: 1.14 +/- 0.06 Ir per IEC 60947-4-1
  • Network type: AC / DC
  • Network frequency: 0...400 Hz
  • Rated voltage [ue]: 690 V AC for power circuit per IEC 60947-4-1
  • Rated insulation voltage [ui]: 690 V per IEC 60947-4-1; 600 V per UL / CSA
  • Rated impulse withstand voltage [uimp]: 6 kV
  • Auxiliary contact: 1 NO + 1 NC
  • Thermal current [ith]: 5 A for signal circuit
  • Associated fuse: 4 A gG / 4 A BS for signal circuit
  • Control: Red button (stop), Blue button (reset)
  • Connection type: Screw terminal blocks - power circuit 1 cable 1...6 mm² single-core; control circuit 2 cables 1...2.5 mm²
  • Tightening torque: 1.7 N.m (power and control circuits)
  • Compatible contactors: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38
  • Mounting: Below contactor, plate or DIN rail (with accessories)
  • Dimensions (W x H x D): 45 x 66 x 70 mm
  • Weight: 0.124 kg
  • IP protection: IP20 per IEC 60529
  • Operating temperature: -20...60°C per IEC 60947-4-1
  • Storage temperature: -60...70°C
  • Dielectric strength: 1.89 kV at 50 Hz per IEC 60947-1
  • Flame resistance: V1 per UL 94
  • Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA

Features and benefits:

  • Phase loss sensitivity: triggers at 130% of Ir with two phases active and the third at zero
  • Temperature compensation across -20...60°C ensures consistent tripping characteristics
  • Direct mounting below TeSys D contactors reduces panel space and wiring
  • Vibration resistance to 6 Gn and shock resistance to 15 Gn for 11 ms suits demanding industrial environments
  • Wide certification portfolio including ATEX INERIS and marine classifications (DNV-GL, RINA, LROS)

Applications:

  • Protection of small fractional-horsepower motors in conveyor and automation systems
  • Motor starter assemblies paired with TeSys D LC1D contactors in control panels
  • HVAC and pump motor circuits requiring reliable thermal overload protection
  • Marine and hazardous-area installations requiring ATEX or marine-certified components

Compliant with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and EN 50495. Part of the Schneider Electric TeSys Deca range.