Schneider LR2K0310 TeSys K Overload Relay 2.6-3.7A Class 10A Direct Mount
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric LR2K0310 is a TeSys K differential thermal overload relay for motor protection, with a current setting range of 2.6 to 3.7 A and Class 10A tripping per IEC 60947-4-1. It mounts directly below TeSys K contactors (LC1K, LC7K, LP1K, LP4K) and operates on both AC and DC networks.
Technical specifications:
- Commercial reference: LR2K0310
- Manufacturer: Schneider Electric
- EAN:
- Series / range: TeSys K (TeSys LRK)
- Product type: Differential thermal overload relay
- Relay use: Motor protection
- Thermal overload setting: 2.6...3.7 A
- Tripping class: Class 10A per IEC 60947-4-1
- Network type: AC / DC
- Rated insulation voltage [Ui]: 690 V per IEC 60947; 750 V per VDE 0110 group C; 600 V per CSA C22.2 No 14
- Rated impulse withstand voltage [Uimp]: 6 kV
- Auxiliary contacts: 1 NO + 1 NC
- Allowable thermal current [Ith]: 6 A (signal circuit)
- Phase loss sensitivity: Yes, per IEC 60947-4-1
- Mounting: Below contactor; panel or DIN rail with separate accessories
- Connection: Screw terminal blocks, 1.5...4 mm² solid, 0.75...4 mm² flexible
- Tightening torque: 1.3 N.m
- Dimensions (WxHxD): 45 x 58 x 65 mm
- Weight: 0.145 kg
- IP rating: IP2x per IEC 60529
- Operating temperature: -20...55°C (without characteristic change) per IEC 60947
- Storage temperature: -40...70°C
- Standards: IEC 60947, VDE 0660, BS 4941, NF C 63-650
- Certifications: UL, CSA, UKCA
Features and benefits:
- Differential thermal trip mechanism protects motors reliably across AC and DC networks up to 400 Hz
- Phase loss sensitivity detects single-phase conditions per IEC 60947-4-1, preventing motor damage
- Selectable manual or automatic reset via front-mounted selector switch for flexible operation
- Yellow trip indicator provides clear local fault signaling at a glance
- Direct-mount design below TeSys K contactors enables compact, wiring-efficient panel assemblies
Applications:
- Motor overload protection in motor control centers and direct-on-line starter assemblies
- Reversing starter panels for industrial machinery and conveyor drives
- Pump and fan motor protection in HVAC and building services installations
- Compressor and mixer drive protection in manufacturing and process plants
Compliant with IEC 60947, VDE 0660, BS 4941, and NF C 63-650. Part of the Schneider Electric TeSys K range.
Also known as: Schneider LR2K0310, Schneider Electric LR2K0310, TeSys K overload relay, thermal motor protection relay 2.6-3.7A.