Schneider C11B3TM050L ComPacT NSXm Trip Unit 3P 50 A TMD
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric C11B3TM050L is a ComPacT NSXm 100B 3-pole circuit breaker rated at 50 A with a TMD (thermal-magnetic) trip unit and EverLink lug terminals. Designed for electrical power distribution, it delivers an ultimate short-circuit breaking capacity of 25 kA at 415 V AC, making it suitable for demanding industrial and commercial panel applications.
Technical specifications:
- Commercial reference: C11B3TM050L
- Manufacturer: Schneider Electric
- EAN:
- Series / range: ComPacT NSXm new generation
- Product type: Circuit breaker
- Number of poles: 3P (3 protected poles)
- Rated current [In]: 50 A at 40 °C
- Rated voltage [Ue]: 690 V AC 50/60 Hz
- Network type: AC, 50/60 Hz
- Ultimate breaking capacity [Icu]: 50 kA at 220-240 V AC / 25 kA at 380-415 V AC / 20 kA at 440 V AC / 10 kA at 500 V AC (IEC 60947-2)
- Service breaking capacity [Ics]: 50 kA at 220-240 V AC / 25 kA at 380-415 V AC / 20 kA at 440 V AC / 10 kA at 500 V AC (IEC 60947-2)
- Performance level: B - 25 kA at 415 V AC
- Trip unit name: TM-D
- Trip unit technology: Thermal-magnetic
- Long-time pick-up adjustment [Ir]: 0.7-1 x In (adjustable)
- Instantaneous pick-up [Ii]: 600 A (fixed)
- Rated insulation voltage [Ui]: 800 V AC 50/60 Hz
- Rated impulse withstand voltage [Uimp]: 8 kV
- Mounting: Fixed, back plate
- Connection terminals: EverLink lug 2.5-95 mm² solid/stranded aluminium/copper; 2.5-70 mm² flexible copper
- IP protection rating: IP40 (IEC 60529)
- IK impact rating: IK07 (IEC 62262)
- Operating temperature: -25 to 70 °C
- Storage temperature: -50 to 85 °C
- Relative humidity: 0-95%
- Operating altitude: up to 2000 m without derating; up to 5000 m with derating
- Dimensions (W x H x D): 81 x 137 x 80 mm
- Weight: 1.06 kg
- Mechanical endurance: 20,000 cycles
- Electrical endurance: 20,000 cycles at 440 V In/2
- Standard: EN/IEC 60947
- Use category: Category A
Features and benefits:
- High breaking capacity of 25 kA at 415 V AC enables use in high fault-current environments without requiring additional current-limiting devices
- EverLink lug terminals accept wide conductor range (2.5-95 mm²) in aluminium or copper, simplifying installation and cable management
- Adjustable long-time pick-up (0.7-1 x In) allows fine-tuning of thermal protection to match actual load characteristics
- Compact 9-module DIN width with horizontal and vertical handle mounting positions provides flexible panel layout options
- One slot each for auxiliary contact (OF), alarm contact (SD), and voltage release (MN or MX) enables easy monitoring and remote tripping integration
- Halogen-free plastic parts and PVC-free construction support environmental compliance requirements
Applications:
- Main and outgoing circuit protection in industrial distribution boards and motor control centres
- Feeder protection in commercial buildings, data centres, and infrastructure switchboards
- Protection of sub-distribution panels in manufacturing facilities where high fault levels are present
- Machine builder panels requiring compact footprint with high breaking performance
Compliant with EN/IEC 60947 and IEC 60947-2. Part of the Schneider Electric ComPacT NSXm new generation range.
Also known as: Schneider C11B3TM050L, Schneider Electric C11B3TM050L, NSXm 50A 3P circuit breaker, ComPacT NSXm TMD 50A.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.