Schneider C103TM100 ComPacT NSX100 Trip Unit 3P 100 A TMD
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric C103TM100 is a TM-D thermal-magnetic trip unit for ComPacT NSX100/160/250 moulded case circuit breakers, rated at 100 A at 40°C across 3 poles. It provides overload (thermal) and short-circuit (magnetic) protection for AC power distribution applications up to 690 V AC.
Technical specifications:
- Commercial reference: C103TM100
- Manufacturer: Schneider Electric
- EAN:
- Series / range: ComPacT NSX new generation
- Product type: Trip unit
- Trip unit name: TM-D
- Trip unit technology: Thermal-magnetic
- Compatible circuit breakers: ComPacT NSX100, NSX160, NSX250 (new generation)
- Number of poles: 3P
- Protected poles: 3d
- Trip unit function: Li (overload + instantaneous short-circuit)
- Rated current (Ir): 100 A at 40°C
- Rated voltage (Ue): 690 V AC 50/60 Hz
- Network type: AC
- Network frequency: 50/60 Hz
- Long-time pick-up adjustment (Ir): Adjustable, 0.7...1 x In
- Long-time delay (tr): Fixed, 120...400 s at 1.5 x In; 15 s at 6 x Ir
- Instantaneous protection (Ii): Fixed, 800 A
- Differential protection: None
- Mounting: Fixed
- IP protection rating: IP40 (IEC 60529)
- Pollution degree: 3 (IEC 60947-1)
- Operating temperature: -25...70°C
- Storage temperature: -50...85°C
- Electrical shock protection class: Class II
- Standard: EN/IEC 60947-2
- Package weight: 390 g
Features and benefits:
- Adjustable long-time thermal pick-up (0.7...1 x In) allows calibration to match connected load requirements
- Fixed instantaneous short-circuit protection set at 800 A for reliable fault clearing
- Compatible with ComPacT NSX100, NSX160, and NSX250 frames, offering flexibility across multiple breaker ratings
- IP40 enclosure and pollution degree 3 rating suit industrial panel environments
- Wide operating temperature range (-25...70°C) supports demanding installation conditions
Applications:
- Industrial power distribution panels requiring overload and short-circuit protection
- Retrofit or replacement trip unit in existing ComPacT NSX100/160/250 circuit breaker frames
- Main or sub-distribution boards in commercial and industrial facilities
- Feeder protection in motor control centres and switchgear assemblies
Compliant with EN/IEC 60947-2. Part of the Schneider Electric ComPacT NSX new generation range.
Also known as: Schneider C103TM100, Schneider Electric C103TM100, NSX100 trip unit, TM-D thermal-magnetic trip unit.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.