59641 8 temperature sensor module MET148-2 for Sepam series 20, 40, 60, 80
External 8 temperature sensors module MET148-2 for Schneider Electric's protection relays. This module can be used to ensure direct temperature measurements with Resistance Temperature Detectors (RTDs). It can be connected to the protection relay any time: during installation, commissioning or even during maintenance. This module provides 8 Resistance Temperature Detector (RTD) inputs. External modules allow late versionizing for Partners and assure expandability of PowerLogic P5 features for End Users. This external module can work with Pt100, Ni100 and Ni120 types of Resistance Temperature Detectors. Connection is made thru screw-type terminals. This module does not require auxiliary power supply. It is powered by PowerLogic P5. The product dimensions are 88 mm in height (3.46 in), 144 mm in width (5.70 in) and 30 mm in depth 1.18 in) for a net weight of 200 g (0.440 lbs). PowerLogic P5 is compliant with EN 60255-26, EN 60255-27 standard and with UL Standard. It provides Marine certification. This product can be installed on symmetrical DIN rail. Connection cords (59660, 59661, 59662). Connection cords (59660, 59661, 59662).