Hager SBN363 SBN Load Break Switch 3P 63 A DIN Rail
Free Shipping
Get free shipping on orders exceeding €300!
The Hager SBN363 is a 3-pole load break switch (disconnector) rated at 63 A, designed for safe isolation of electrical circuits on 400 V AC systems. It carries an insulation voltage of 440 V and an impulse withstand voltage of 6,000 V, and mounts directly on a DIN rail in modular distribution boards and control panels.
Technical specifications:
- Catalog reference: SBN363
- Manufacturer: Hager
- Product type: 3-pole load break switch (disconnector)
- Rated current (Ue): 63 A
- Rated operational voltage: 400 V AC
- Insulation voltage (Ui): 440 V
- Impulse withstand voltage (Uimp): 6,000 V
- Making capacity (Icm) at 415 V AC per IEC 60947-3: 1.33 kA
- Rated short-time current (Icw, 1 s): 0.94 kA
- Conditional short-circuit current (Inc) with fuse per IEC/EN 60669-2-4: 6,000 A / 80 A gG parallel 32 A gG
- Frequency: 50 - 60 Hz
- Number of poles: 3P
- Number of modules: 3
- NO contacts: 3 / NC contacts: 0
- IP rating: IP20
- Dimensions (H x W x D): 83 x 52.50 x 68 mm
- Cable connection - flexible conductor: 2.5 - 16 mm²
- Cable connection - rigid conductor: 2.5 - 25 mm²
- Nominal torque: 2.80 Nm
- Operating temperature: -20 to 70°C
- Storage/transport temperature: -40 to 80°C
- Lower terminal type: biconnect (for modular devices)
- DIN rail compatible: Yes
- RoHS compliant: Yes
- REACh-SVHC free: Yes
Features and benefits:
- biconnect lower terminals allow flexible wiring configurations within modular DIN rail assemblies.
- Aligned upper and lower terminals simplify installation and cable management in distribution boards.
- Mechanical life of 60,000 operations and electrical life of 5,000 operations at rated load in AC21 and AC22 duty.
- Wide operating temperature range (-20 to 70°C) supports use in demanding environments.
- RoHS compliant and REACh-SVHC free, meeting current environmental standards.
Applications:
- Load isolation and safe disconnection in residential and commercial distribution boards.
- Three-phase circuit isolation in industrial control panels and motor switching applications (AC21, AC22).
- Modular switchboard assemblies requiring DIN rail-mounted disconnectors.
- Installations requiring conditional short-circuit protection in series with fuses.
Also known as: Hager SBN363, 3-pole disconnector switch 63 A, DIN rail load break switch 63 A.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.