The Circutor CVM-C11 (code M58541) is a panel-mounted power analyser designed for standard 96 x 96 mm cutouts, measuring electrical energy quality variables across four input channels. It analyses individual voltage and current harmonics up to the 31st order and communicates over RS-485 using Modbus RTU or BACnet. With four-quadrant measurement capability covering both consumption and generation, it suits low- and medium-voltage installations including those with photovoltaic or backup generation.
Technical specifications:
- Model: CVM-C11
- Full model code: CVM-C11-ITF-IN-485-ICT2
- Circutor code: M58541
- EAN: 8433059359225
- Mounting: Panel, 96 x 96 mm
- Dimensions (W x H x D): 96 x 96 x 67.2 mm
- Weight: 0.363 kg
- AC supply voltage: 100-270 V AC, ±10%, 50-60 Hz
- DC supply voltage: 100-270 V DC, ±10%
- Supply installation category: CAT III 300 V
- Supply consumption: 2-5 VA
- Nominal current input: .../5 A or .../1 A
- Minimum measurable current: 10 mA
- Current measurement accuracy: 0.2% (1-120% In)
- Measuring channels: 4
- Nominal voltage: 230 V Ph-N / 380 V Ph-Ph
- Voltage measurement range: 10 V to 300 V F-N / 520 V F-F
- Voltage input impedance: greater than 1.7 MΩ
- Voltage measurement accuracy: 0.2% (5-120% Un)
- Frequency range: 45-65 Hz
- Harmonic analysis: up to 31st order
- Active power accuracy: 0.5% ±2 digit
- Reactive power accuracy: 1% ±2 digit
- Power factor accuracy: 0.5%
- Communication protocol: Modbus RTU / BACnet
- Communication interface: RS-485
- Digital inputs: 2, NPN, 2000 V isolation
- Relay outputs: 2, max 625 VA / 75 W (AC1), mechanical life 10x10^6 cycles
- Transistor outputs: 2, NPN, 24 V DC, max 50 mA, 16 imp/s, pulse width 30-400 ms (programmable)
- Front protection: IP 54
- Impact resistance: IK 08
- Enclosure material: Self-extinguishing V0 plastic
- Working temperature: -25 to +70 °C
- Storage temperature: -25 to +75 °C
- Relative humidity: 5-95% (non-condensing)
- Pollution resistance: 2
- Maximum installation height: 2000 m
- Display: Backlit LCD (Custom COG)
- Keyboard: 3 keys
- LEDs: 2
- Standards: EN IEC 61326-1, EN IEC 61557-12, EN 61010-1, EN 61010-2-030, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, UL 94, UNE-EN 60068-2-1, UNE-EN 60068-2-2, UNE-EN 60068-2-78
Features and benefits:
- Four-quadrant measurement (Q1-Q4) handles both energy consumption and generation, making it compatible with grid-tied solar PV and backup generator setups.
- Neutral current measurement enables detection of phase imbalance and overloads on the neutral conductor, supporting safer installation monitoring.
- Three-tariff energy discrimination via two digital inputs allows consumption to be allocated by work shift or energy source - grid, generator, or photovoltaic generation.
- Configurable alarm control with 2 relay outputs and 2 NPN transistor outputs can trigger on any instantaneous measured or calculated parameter, with adjustable hysteresis, NO/NC selection, connection and disconnection delays, and interlock settings.
- On-screen CO2 emission and energy cost tracking per tariff, alongside graphical display of instantaneous active power and all four quadrants, with numerical cos/PF indication.
Applications:
- Power quality monitoring in industrial switchboards, including THD measurement and harmonic analysis to the 31st for each phase of voltage and current.
- Multi-source energy accounting in facilities combining mains supply with solar PV generation or diesel generators, using tariff discrimination to separate consumption by source.
- Shift-based energy cost tracking in manufacturing environments, using three-tariff mode to allocate consumption across different production periods.
- Alarm and protection schemes in low- and medium-voltage panels, using relay and transistor outputs to signal out-of-tolerance power quality conditions or energy thresholds.
Also known as: Circutor CVM-C11, CVM-C11 M58541, CVM-C11-ITF-IN-485-ICT2, panel power analyser RS-485 Modbus, Circutor M58541 power analyser.