Schneider LV540306 circuit breaker EasyPact CVS400F
Free Shipping
Get free shipping on orders exceeding €300!
The Schneider Electric LV540306 (CVS400F TM400D) is a 3-pole thermomagnetic circuit breaker from the EasyPact CVS range, rated 400 A at 40°C for AC power distribution. It delivers a breaking capacity of 36 kA at 380/415 V AC per IEC 60947-2, combining short-circuit and thermal overload protection in a fixed-mount design for industrial switchgear.
Technical specifications:
- Commercial reference: LV540306
- Manufacturer: Schneider Electric
- EAN:
- Series / range: EasyPact CVS
- Number of poles: 3P, 3 protected poles
- Rated current [In]: 400 A at 40°C
- Network type: AC, 50/60 Hz
- Usage category: Category A
- Breaking capacity [Icu]: 40 kA at 220/240 V AC, 36 kA at 380/415 V AC, 30 kA at 440 V AC (IEC 60947-2)
- Service breaking capacity [Ics]: 40 kA at 220/240 V AC, 36 kA at 380/415 V AC, 23 kA at 440 V AC
- Breaking capacity code: F
- Protection unit: TM-D thermomagnetic, 400 A at 40°C
- Thermal overload adjustment: 280...400 A
- Instantaneous short-circuit threshold: 5...10 x In (adjustable)
- Rated impulse withstand voltage [Uimp]: 8 kV (EN/IEC 60947-2)
- Mechanical durability: 15,000 cycles
- Electrical durability: 6,000 cycles at 415 V In (IEC 60947-2)
- Control: Handle
- Mounting: Fixed, back plate
- Connection type: Screw terminal, front (upper and lower)
- Dimensions (W x H x D): 140 x 255 x 110 mm
- Weight: 4.7 kg
- IP protection rating: IP40
- Electrical shock protection class: Class II
- Pollution degree: 3 (IEC 60664-1)
- Operating temperature: -25...70°C
- Storage temperature: -50...85°C
- Standards: EN 60947-2, IEC 60947-2
- Certifications: GOST, IEC
Features and benefits:
- TM-D thermomagnetic protection unit provides simultaneous short-circuit and thermal overload protection
- Adjustable thermal overload threshold (280...400 A) and adjustable instantaneous short-circuit threshold (5...10 x In) allow calibration to specific load requirements
- High mechanical durability of 15,000 cycles ensures long service life in demanding installations
- Contact position indicator enables quick visual status verification
- Wide operating temperature range of -25...70°C suitable for varied industrial environments
Applications:
- Main and sub-distribution boards in industrial facilities
- Low-voltage power distribution switchgear and panel assemblies
- Cable and busbar protection in commercial building electrical installations
- Power distribution panels requiring high breaking capacity protection
Compliant with EN 60947-2 and IEC 60947-2. Part of the Schneider Electric EasyPact CVS range.
Also known as: Schneider LV540306, Schneider Electric LV540306, CVS400F 400A 3P circuit breaker, EasyPact CVS400F TM400D.
When sold out, you can still preorder by requesting a quote below.
Important
The images shown are for illustration purposes only and may not be an exact
representation of the product.